LIST NO. 21
Flat base-twin skin |
 |
PRICES CURRENTLY SHOWN AS 2006 - PLEASE APPLY A FACTOR OF x 1.3 AS A GUIDE TO CURRENT JUNE 2010 PRICES
| | CONSTRUCTION | Vertical cylindrical double shell and base plates, single skin roof | | SPILLAGE VOLUME | 110% (min) of gross product volume | | DESIGN CODE | BS799 pt 5,Type 'G' and generally to BS2654:1989/BSEN14015 | | CAPACITY RANGE | 10-200 cubic metres | | STEEL GRADE | BSEN 10 025 S275, 6mm/8mm | | WELDING | Manual metallic arc | | TESTING | - inner | Air. Hydrostatic and radiography at extra cost | | | - outer | Air test | | FITTINGS | To customer choice-see list overleaf and Integ list no.20 | | FINISH | - internal | Self colour, cleaned out | | | - external | Wirebrushed, primer painted. Special long life paint systems are available(list no.130) | OPTIONAL FEATURES | Heating coils, insulation, gauges, switches, overfill alarm, special linings and coatings, interconnecting walkways. | | QUALITY ASSURANCE | Level 'A', refer to List No.140 for details |
With growing demand for environmental protection, advantages of Integ 'Twin Skin' double integrity fuel oil and chemical storage tanks are increasingly recognised. Open spillage bunds present hazards and drainage problems, eliminated entirely by containing spilled fuels and noxious liquids inside their own integral bund compartments. Significant open bund space and civil cost savings can be achieved. | Prices for shop fabricated tanks are ex works. Delivery costs will quoted on request. Add cost of manways, flanged/socket connections etc. as listed below, to basic tank cost 'A'
NOMINAL CAPACITY | ACTUAL GROSS CAPACITY | DIMENSIONS | TANK WEIGHT EMPTY | BASIC TANK PRICE | OPTIONAL EXTRAS-ADD TO BASIC TANK PRICE 'A' | | DIAMETER | SHELL HEIGHT | HYDRO- TEST | RADIO- GRAPHY | CAGED LADDER | HAND RAILS | EXT'L PAINT | | INNER | OUTER | | M3 | M3 | GALLS | MM | MM | MM | KG | £(A) | £(B) | £(C) | £(D) | £(E) | £(F) | 10 | 9.4 | 2074 | 2000 | 2100 | 3000 | 2400 | 6351 | 176 | 319 | 579 | 566 | 904 | 12 | 12.5 | 2765 | 2000 | 2100 | 4000 | 2600 | 6962 | 176 | 319 | 806 | 566 | 1157 | 16 | 16.6 | 3657 | 2300 | 2400 | 4000 | 3100 | 7696 | 176 | 345 | 806 | 637 | 1281 | 20 | 20.7 | 4571 | 2300 | 2400 | 5000 | 3900 | 8431 | 176 | 390 | 995 | 637 | 1573 | 25 | 24.5 | 5400 | 2500 | 2600 | 5000 | 4400 | 9458 | 176 | 403 | 995 | 767 | 1723 | 30 | 30.8 | 6775 | 2800 | 2900 | 5000 | 5000 | 10719 | 221 | 416 | 995 | 884 | 1892 | 40 | 42.4 | 9333 | 3000 | 3200 | 6000 | 7300 | 12188 | 260 | 475 | 1105 | 923 | 2464 | 50 | 49.5 | 10888 | 3000 | 3200 | 7000 | 7900 | 14697 | 260 | 488 | 1183 | 923 | 2808 | 60 | 62.5 | 13761 | 3500 | 3700 | 6500 | 8600 | 17336 | 312 | 501 | 1183 | 975 | 3088 | 70 | 72.2 | 15878 | 3500 | 3700 | 7500 | 9500 | 19539 | 345 | 527 | 1242 | 975 | 3497 | 80 | 81.7 | 17974 | 4000 | 4200 | 6500 | 10300 | 23212 | 397 | 527 | 1261 | 1001 | 3614 | 100 | 100.5 | 22122 | 4000 | 4200 | 8000 | 11800 | 24577 | 429 | 527 | 1424 | 1001 | 4264 | 125 | 125.7 | 27652 | 4000 | 4200 | 10000 | 13800 | 28652 | 527 | 527 | 1781 | 1001 | 5174 | 150 | 150.8 | 33179 | 4000 | 4200 | 12000 | 15900 | 35419 | 631 | 696 | 2659 | 1001 | 6201 | 175 | 175.9 | 38709 | 4000 | 4200 | 14000 | 18000 | 40131 | 735 | 696 | 3094 | 1001 | 7235 | 200 | 201.1 | 44239 | 4000 | 4200 | 16000 | 20200 | 45019 | 839 | 696 | 3452 | 1001 | 8275 |
£(A) Shop fabricated and tested, ex works, loaded on transport. £(B) Extra cost for hydrostatic test and certification £(C) Extra cost for weld radiography to BS2654/BSEN14015 with interpretation. £(D) Extra cost for vertical caged access ladder, primer painted. Add 35% for galvanising. £(E) Extra cost for full set handrailing. Add 35% for galvanising. £(F) Extra cost for external surfaces shotblast SA 2.5 with shop or site applied long life 3 coat epoxy paint system at 185 microns dft. Alternative paint systems are offered. See Integ No.130
| MANWAYS | MANWAY DIAMETER | | 460mm | 600mm | 800mm | | ROOF | INTEG STD | 332 | 468 | 819 | | MANWAY | BS2654 | - | 904 | 1599 | | SHELL | INTEG STD | 787 | 949 | 1339 | | MANWAY | BS2654 | - | 1547 | 2574 | | MANWAY | HINGE | 59 | 59 | 91 | | EXTRAS | DAVIT ARM | 228 | 228 | 286 |
| TANK FITTINGS | | SIZE | PRICE £ | SIZE | PRIZES £ | NB | BS 4504 | ASA 150 | NB | BS 4504 | ASA 150 | | Flanged Connection | Drilled BS4505 or ASA 150 RF with 100 standout | 25 | 111 | 117 | 150 | 345 | 390 | 40 | 143 | 150 | 200 | 501 | 527 | 50 | 150 | 163 | 250 | 663 | 715 | 65 | 176 | 215 | 300 | 891 | 943 | 80 | 215 | 247 | 350 | 1196 | 1268 | 100 | 286 | 319 | 400 | 1326 | 1385 | | Screwed Connection | Additional BSP welded socket with dust protection cap | 15-50 | 39 | 65-80 | 65 | 100 | 91 | | Studded Pad | Single faced and studded pad for gauge/switch connection | 50 | 143 | 80 | 189 | 100 | 215 |
Heating coils, contents gauges, dip hatches, vents, flame arresters, overfill alarms etc. are listed on companion Integ price sheets.
Integ List No. 130 details special tank lining and coating systems to accommodate a wide variety of contents and environmental conditions.
Integ List No. 90 covers insulation systems which can apply
Diameters and heights listed above are typical and can easily be varied to suit size, height limitations, and capacity required. Specific quotations will be submitted by return, on request.