- STANDARD TANKS | | CONSTRUCTION | Horizontal cylindrical, dished ends, of 'twin skin' design | | DESIGN CODE | BS799 Pt 5, Type 'A' and generally BS2594/BSEN 12285-2 | | CAPACITY RANGE | 2300-54100 litres. Outer skin to contain minimum of 110% of gross tank capacity | | STEEL GRADE | BSEN 10 025 S275 | | STEEL THICKNESS (See Table) | Inner tank shell 6, 8, 10mm. Ends 6, 8mm Outer tank shell 4mm. Ends 5mm. | | TESTING | Inner tank air 0.7 barG (10 psig}. Hydro test at extra cost. Outer tank air 0.14 barG (2 psig) | | STANDARD FITTINGS | 1 - 450 dia shell manway, cover and gasket 2 - 50 NB sockets for fill and vent 2 - 40 NB sockets for outlet and drain 1 - Combined tank and bund vent with cowl 1 - 300 dia leak detection sump with switch pad 2 - Lifting lugs | | FINISH-internal | Self colour, cleaned out | - external
| Wirebrush, 1 coat red oxide primer paint 25 microns dft | | OPTIONAL EXTRAS | Graduated diprod, contents gauge, level switch, leak detection system, overfill alarm, access ladder and platform, special internal/external paint finishes | | QUALITY ASSURANCE | Level 'A', refer to List No. 140 for details |
TYPICAL FITTINGS. Prices of fittings not listed quoted on request |
 |
DIP AND VENT
| MANWAYS | STANDARD CONNECTIONS |  |  |  |
To give access to tank manholes for dipping or product sampling, fabricated ladders and platforms are available, match fitted at Works. These are designed to conform with current safety regulations and are supplied self colour.
Prices as listed. Add 25% if ladders are to be hot dip galvanised. A full range of stairways, ladders, interconnecting walkways, bund ladders and handrailing is detailed on List 100. Or to special design. | 
|
Prices listed are ex works. Delivery costs will be quoted on request | CAPACITY | DIMENSIONS(OUTER) | BS799 TANKS | BS2594 TANKS | EXTRA FEATURES | | NORMAL | ACTUAL | DIAM | SHELL | O'ALL | WEIGHT | SADDLES REQ'D | PRICE | WEIGHT | SADDLES REQ'D | PRICE | PAINT SYST '1' | PAINT SYST '2' | PAINT SYST '3' | | GALLS | M3 | M3 | MM | MM | MM | KG | NO. | £'A' | KG | NO. | £ 'B' | £ 'C' | £ 'D' | £ 'E' | | 1000 | 4.5 | 4.51 | 1400 | 3350 | 3762 | 1690 | 2 | 3809 | 1690 | 2 | 3809 | 332 | 527 | 46 | | 1500 | 6.9 | 7.31 | 1553 | 4400 | 4818 | 2333 | 2 | 4667 | 2333 | 2 | 4667 | 468 | 728 | 52 | | 2000 | 9.1 | 9.42 | 2028 | 3300 | 3812 | 2514 | 2 | 5090 | 2514 | 2 | 5090 | 533 | 819 | 59 | | 3000 | 13.6 | 14.14 | 2028 | 4900 | 5467 | 3265 | 2 | 6045 | 3265 | 2 | 6045 | 709 | 1105 | 85 | | 4000 | 18.1 | 18.71 | 2468 | 4400 | 5049 | 3765 | 2 | 6819 | 3765 | 2 | 6819 | 761 | 1170 | 98 | | 5000 | 23.2 | 22.87 | 2468 | 5379 | 6028 | 4432 | 2 | 7774 | 5180 | 2 | 7774 | 969 | 1502 | 137 | | 6000 | 27.7 | 28.06 | 2468 | 6600 | 7249 | 5080 | 2 | 8548 | 5970 | 2 | 9737 | 1131 | 1755 | 163 | | 7000 | 31.8 | 32.67 | 2773 | 6072 | 6809 | 5456 | 2 | 8990 | 6390 | 2 | 9269 | 1235 | 1905 | 189 | | 8000 | 36.5 | 37.52 | 2773 | 6974 | 7711 | 6050 | 3 | 9750 | 7120 | 2 | 11109 | 1359 | 2119 | 215 | | 9000 | 40.5 | 41.70 | 2773 | 7755 | 8486 | 6581 | 3 | 10400 | 7740 | 2 | 11850 | 1482 | 2301 | 234 | | 10000 | 45.4 | 45.47 | 2773 | 8393 | 9124 | 7081 | 3 | 11070 | 8280 | 2 | 12864 | 1573 | 2457 | 254 | | 12000 | 55.1 | 54.60 | 2773 | 10065 | 10802 | 8122 | 4 | 12370 | 9570 | 2 | 13897 | 1833 | 2847 | 306 | | 15000 | 69.6 | 70.80 | 3028 | 11102 | 12045 | 9782 | 4 | 14528 | 11550 | 2 | 16263 | 2197 | 3406 | 397 | | 18000 | 81.8 | 84.00 | 3028 | 13200 | 14223 | 11320 | 5 | 15990 | 15170 | 2 | 20183 | 2555 | 3972 | 468 | | 20000 | 90.6 | 90.70 | 3028 | 14113 | 15136 | 12108 | 5 | 17518 | 16050 | 2 | 21340 | 2704 | 4206 | 494 |
(1) Actual capacities calculated on nominal dimensions without allowance for ullage and are subject to accepted manufacturing tolerances. (2) Price 'A'. Tanks fabricated to BS799 pt. 5:1987, type 'A'
Price 'B'. Tanks fabricated to BS2594:1975, standard construction. Price 'C'. Extra for external surfaces flash blast with one coat zinc phosphate primeG one coat MIO phenolic, one coat high build expoxy. Total 185 microns DFT. Price 'D'. Extra for external surfaces shotblast SA 2 1/2, onecoat epoxy primer, one coat MIO epoxy, one coat wear resistant enamel. Total 200 microns DFT. Price 'E'. Extra for hydrostatic test to BS2594, with certificates. | TANK TYPE | CAPACITY RANGE | THICKNESS (mm) | | SHELL | ENDS | | STANDARDS | | 6 | 6 | | | UP TO 20M | 6 | 6 | | BS2594 | 20-70M3 | 8 | 8 | | | OVER 70M3 | 10 | 8 | | OUTER TANK | ALL TANKS | 4 | 5 |
| Fitting | Description | Tank Nominal Diameter | | 1400 | 1553 | 2028 | 2468 | 3028 | 3660 | | £ | £ | £ | £ | £ | £ | | Support Cradles 150mm high | Loose | 241 | 241 | 319 | 371 | 410 | 618 | | Tack Welded | 137 | 260 | 345 | 403 | 455 | 696 | | Fully Welded | 143 | 306 | 390 | 455 | 501 | 780 | | Bolt Holes (ea) | 8 | 8 | 8 | 8 | 8 | 8 | | Extra 150 height | 26 | 39 | 39 | 39 | 59 | 78 | | Offset Fill Ass'y | As illustrated | 50NB | 384 | 384 | 423 | 423 | 494 | 566 | | 80NB | 546 | 553 | 611 | 611 | 683 | 780 | | Fill and Dip Pipe | Including screwed riser pipe | 50NB | 91 | 111 | 111 | 117 | 130 | 143 | | 65NB | 117 | 137 | 137 | 143 | 150 | 169 | | 80NB | 137 | 150 | 150 | 163 | 163 | 176 | | 100NB | 163 | 163 | 163 | 169 | 176 | 195 | | Ladder as illustrated | 98 | 150 | 325 | 390 | 390 | 507 | | Platform | As illustrated | TYP 1 | 325 | 429 | 475 | 475 | 546 | 670 | | TYP 2 | 423 | 566 | 624 | 624 | 709 | 884 | | Dipstick | Brass 'T' Section | 59 | 91 | 91 | 104 | 111 | 137 | | GRP 'T' Section | 59 | 91 | 91 | 104 | 111 | 137 |
| Connections as illustrated | Prices are £ EA Fully Welded | | NOMINAL BORE | 25 | 40 | 50 | 80 | 100 | 150 | 200 | 250 | 300 | | Full socket | 39 | 59 | 65 | 72 | 91 | - | - | - | - | | BS4504 Flange | 72 | 78 | 124 | 143 | 189 | 273 | 390 | 488 | 683 | | ASA 150 Flange | 65 | 72 | 98 | 130 | 176 | 338 | 345 | 423 | 618 | | Studded Pad | - | - | 104 | 143 | 169 | - | - | - | - | | Hand Valve | 52 | 78 | 104 | 163 | 208 | 371 | - | - | - |
| Tank Dia | Capacity per 300mm | Cost per 300mm | Comp't | | 6mm | 8mm | MM | LITRES | £ | £ | £ | 1400 | 443 | 85 | 917 | - | 1553 | 548 | 208 | 995 | - | 2028 | 943 | 260 | 1073 | - | 2468 | 1403 | 377 | 1235 | 1495 | 2773 | 1776 | 429 | 1320 | 1547 | 3028 | 2121 | 540 | 1482 | 1755 |
Manway/ Type | Manway diam mm | 460 £ | 500 £ | 600 £ | | Standard | 247 | 273 | 306 | | BS2594 | 319 | 345 | 397 | | Manway Extras | Per 25 mm of neck | 14 | 22 | 29 | | Hinges | 91 | 91 | 91 | | Davit | 195 | 195 | 195 |
|  | Fabricated mild steel support cradles (saddles) can be supplied loose or welded to tank shell. Cradles give 150mm ciearance under the tank barrel. Higher cradles can be supplied at prices listed. Max 1m height. Details of cradles positions should be obtained before concrete piers or boltholes are cast. | | TANK DIA | CRADLE DIMENSIONS | BOLT HOLE DIA | CRADLE POS'N | CRADLE WEIGHT | | 'D' | 'L' | 'W' | 'A' | | MM | MM | MM | MM | MM | KG | 1372 | 1200 | 150 | 14 | 343 | 69 | 1525 | 1330 | 200 | 14 | 380 | 75 | 1830 | 1595 | 200 | 14 | 457 | 101 | 2135 | 1860 | 250 | 18 | 534 | 117 | 2287 | 1990 | 300 | 18 | 572 | 125 | 2440 | 2120 | 300 | 22 | 610 | 160 | 2745 | 2390 | 300 | 22 | 686 | 182 | 3000 | 2610 | 300 | 22 | 750 | 205 | 3660 | 3180 | 300 | 26 | 915 | 276 |
|
Standard tanks are fitted with screwed sockets for vent, fill, outlet and drain. Extra prices are listed for BST and ASA 150 flanged nozzles and a choice of davit and hinged manways as well as faced and studded pads. Other special fittings will be quoted on request. Freight costs to distant sites sometimes make it preferable to ship tanks in prefabricated 'knock down' form. In such cases INTEG can weld and test on arrival at site, or supervise construction by others.
The standard finish included in tank prices is one coat of red oxide primer on hot rolled steel. It is undoubtedly preferable to remove mill scale and rust particles by shot blasting tank external surfaces at works, followed before oxidation sets in by application of primer and subsequent finishing coats. Extra prices are listed for special finishes in List No. 130
For viscous liquids it may be necessary to fit heating coils to achieve satisfactory product flow. These can be of fixed or withdrawable design, plain or finned surface, carbon or stainless steel to suit application. INTEG will design your coils for you, to achieve required heat up rate. Insulation can also be fitted at works or on site.Refer to List No. 90
To determine tank contents, GRP or brass graduated dipsticks can be used. Or a variety of direct or remote reading gauges employed. Refer to price list no.110 for a selection of gauges and switches available.
|
|